Abstract
This paper presents the use of real-time digital simulator (RTDS) and hardware-in-the-loop (HIL) methods for the validation of an energy management system designed for real low-voltage (LV) distribution networks with a high penetration of renewable energy sources. The system is used to address voltage violations and current overloading issues and allows the network operator to maintain safe and controllable network operations. The applied control strategy and the system software were verified by means of simulations. In this paper, the next stage of system validation using the HIL method is presented. A testbed was designed and developed to test the operation of prototype controllers of the system in flexible and reproducible conditions before installing them in the network. The presented testing platform not only includes the LV network simulator with the power amplifiers needed for closed-loop setup but also additional elements of a real network to which the system is dedicated, i.e., the advanced metering infrastructure, photovoltaic source, and energy storage inverters and load devices. Furthermore, the real cellular network of the distribution network operator is used in the communication between the controllers. In addition, the article contains discussions on communication issues, including limitations related to selected protocols. Finally, examples of the experimental validation of the controller prototypes are presented.