Abstract
An excessive increase in reactive power consumption is unfavorable from the point of view of a power system. For this reason, devices compensating reactive power consumption are used. The capacitor is one such device. Capacitors must be tested regularly during their exploitation. One of the activities that should be performed is testing the degree of heating of the cells of a capacitor bank. Thermography can be used to perform such tests. This non-contact method has its limitations. Due to the angular emissivity and the change in the distance between the lens and the object under observation, the temperature measured with a thermographic camera may differ from the actual temperature. This phenomenon is visible on cylindrical capacitor cases. Consequently, depending on the location of the observation point on the capacitor case, the result of the thermographic temperature measurement may be different. To investigate this phenomenon, experimental work has been undertaken.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献