Abstract
Abstract
The paper presents the results of data gathering regarding the heat recovery efficiencies of different heat recovery types at various air flows supplied by some of the most common manufacturers. The study showed that the average heat recovery efficiency of modern, commonly used rotary heat exchangers is around 83% while for counter-flow exchangers around 86%. Also, in the paper, the simulation results of heat energy consumption and recovered heat potential for the single-family house are presented. The simulations are performed in IDA-ICE software and show that for the specific building it is possible to reduce the heating energy up to 84% if ventilation with heat recovery is used. The results also showed that in case the internal heat loads decrease, then it slightly affects the heat recovery potential. In the case of no internal gains, this value decreases by 4%.
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献