Affiliation:
1. Mechanical Department,Thermal and Fluids Engineering Division, TECNUN-University of Navarra, Paseo de Manuel Lardizábal 13, 20018 San Sebastián, Spain
Abstract
The performance of axial fans in close proximity to the electromagnetic compatibility (EMC) screens was analyzed by means of an experimental parametric study. The following geometrical parameters were studied: the hub-to-tip ratio, the ratio between fan thickness and fan diameter, the porosity and thickness of the perforated plate, and finally, the distance between the perforated plate and the inlet and the outlet of the fan. Screen porosity was found to be the most important parameter. Fan performance degradation is expressed by means of two correlations: one for the deterioration in the fan pressure at the no-flow point and the other for the flow rate reduction at the free delivery point. Both correlations were formulated as functions of screen porosity and the distance between the fan and the screen. We believe that the correlations can serve as a good guide for correct fan placement in a telecommunications cabinet.
Subject
Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献