Comprehensive Experimental and Computational Analysis of a Fully Contained Hybrid Server Cabinet
Author:
Nemati Kourosh1, Alissa Husam A.2, Murray Bruce T.2, Sammakia Bahgat G.2, Tipton Russell3, Seymour Mark J.4
Affiliation:
1. Mechanical Engineering Department, State University of New York, Binghamton, NY 13902 e-mail: 2. Mechanical Engineering Department, State University of New York, Binghamton, NY 13902 3. Emerson Network Power, Columbus, OH 43085 4. Future Facilities, London SE1 7HX, UK
Abstract
The rapid growth in the number of data centers combined with the high-density heat dissipation of computer and telecommunications equipment has made energy efficient thermal management of data centers a key research area. Localized hybrid air–water cooling is one approach to more effectively control the cooling when there is wide variation in the amount of dissipation in neighboring racks while the traditional air cooling approach requires overprovisioning. In a closed, hybrid air–water cooled server cabinet, the generated heat is removed by a self-contained system that does not interact with the room level air cooling system. Here, a hybrid-cooled enclosed cabinet and all its internal components were characterized experimentally in steady-state mode (e.g., experimentally determined heat-exchanger effectiveness and IT characterization). Also, a comprehensive numerical model of the cabinet was developed and validated using the experimental data. The computational model employs full numerical modeling of the cabinet geometry and compact models to represent the servers and the air/water heat exchanger. The compact models were developed based on experimental flow and thermal characterization of the internal components. The cabinet level model has been used to simulate a number of operating scenarios relevant to data center applications such as the effect of air leakage within the cabinet. The effect of the air side and the water side failure of the cooling system on the IT performance were investigated experimentally. A comparison was made of the amount of time required to exceed the operating temperature limit for the two scenarios.
Funder
National Science Foundation
Publisher
ASME International
Subject
Mechanical Engineering,Mechanics of Materials,Condensed Matter Physics,General Materials Science
Reference24 articles.
1. Hybrid Cooling Technology for Large-Scale Computing Systems: From Back to the Future,2011 2. Maintaining Datacom Rack Inlet Air Temperatures With Water Cooled Heat Exchanger,2005 3. Iyengar, M., David, M., Parida, P., Kamath, V., Kochuparambil, B., Graybill, D., Schultz, M., Gaynes, M., Simons, R., Schmidt, R., and Chainer, T., 2012, “Server Liquid Cooling With Chiller-Less Data Center Design to Enable Significant Energy Savings,” 28th Annual IEEE Semiconductor Thermal Measurement and Management Symposium (SEMI-THERM), San Jose, CA, Mar. 18–22, pp. 212–223.10.1109/STHERM.2012.6188851 4. David, M. P., Iyengar, M. K., Parida, P., Simons, R. E., Schultz, M., Gaynes, M., Schmidt, R., and Chainer, T., 2012, “Impact of Operating Conditions on a Chiller-Less Data Center Test Facility With Liquid Cooled Servers,” 13th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), San Diego, CA, May. 30–Jun. 1, pp. 562–573.10.1109/ITHERM.2012.6231480 5. Thermal Performance Metrics for Arranging Forced Air Cooled Servers in a Data Processing Cabinet;ASME J. Electron. Packag.,2005
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
|
|