Investigation of the Mechanism of Temperature Rise in a Data Center With Cold Aisle Containment

Author:

Zhang Mingrui1,Long Zhengwei2,An Qingsong3,Sun Chao4,Zhang Hao2,Cheng Xionglei2,Li Xiaowei5

Affiliation:

1. Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, Tianjin University, Tianjin 300072, China

2. School of Environmental Science and Engineering, Tianjin University, Tianjin 300072, China

3. Key Laboratory of Efficient Utilization of Low and Medium Grade Energy, Tianjin University, Tianjin 300072, China e-mail:

4. School of Computer Science and Technology, Tianjin University, Tianjin 300072, China

5. China Ship Development and Design Center, Wuhan 430064, China

Abstract

This paper theoretically investigates the relationships among factors that affect the temperature rise of server racks and experimentally tests the influence of variable space contained arrangements on the thermal performance. To express the flow and heat transfer process of cold air in servers and analyze the critical factors affecting the temperature rise, a simplified mathematical model representing servers is developed using experimental results. An experiment is conducted within a modular data center in which cold air is supplied from a raised floor. The experiment employed a variable space of cold aisle containment and measured the resulting temperature rise, as well as pressure difference of racks and other parameters, in the simplified mathematical model. By comparing the experimental results and theoretical calculation, the theoretical model is proved to be reasonable and valid. The model predicts that the critical factors affecting the temperature rise of racks consist of static and dynamic pressure difference, total pressure of the fans, geometric structure, power consumption, resistance of doors, and opening area of servers. The result shows that the factor affected by the cold aisle contained system is the static pressure, while for the dynamic pressure difference, the contained architecture has a slight positive effect. Although the average temperature rise is quite decreased in the contained system, the static pressure distribution is nonuniform. A half-contained system which reduced contained space ratio to 50% is measured to cause a 22% increase of the static pressure difference, making a more uniform temperature distribution.

Funder

National Natural Science Foundation of China

Publisher

ASME International

Subject

Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials

Reference27 articles.

1. Trends in Worldwide ICT Electricity Consumption From 2007 to 2012;Comput. Commun.,2014

2. Uptime Institute 2012 Data Center Industry Survey,2013

3. Energy Logic: Reducing Data Center Energy Consumption by Creating Savings That Cascade Across Systems;Emerson Network Power,,2009

4. Evaluation of Air Distribution System's Airflow Performance for Cooling Energy Savings in High-Density Data Centers;Energy Build.,2014