Room Level Modeling of Air Flow in a Contained Data Center Aisle
Author:
Arghode Vaibhav K.1, Joshi Yogendra2
Affiliation:
1. Post Doctoral Fellow
George W. Woodruff School of Mechanical Engineering, Georgia Institute of Technology, Atlanta, GA 30332 e-mail: 2. George W. Woodruff School
of Mechanical Engineering, Georgia Institute of Technology, Atlanta, GA 30332
Abstract
Cold aisle containment is used in air cooled data centers to minimize direct mixing between cold and hot air. Here, we present room level air flow field investigation for open, partially and fully contained cold aisles. Our previous investigation for rack level modeling has shown that consideration of momentum rise above the tile surface, due to acceleration of air through the pores, significantly improves the predictive capability as compared to the generally used porous jump model. The porous jump model only specifies a step pressure loss at the tile surface without any influence on the flow field. The momentum rise could be included by either directly resolving the tile's pore structure or by artificially specifying a momentum source above the tile surface. In the present work, a modified body force model is used to artificially specify the momentum rise above the tile surface. The modified body force model was validated against the experimental data as well as with the model resolving the tile pore geometry at the rack level and then implemented at the room level. With the modified body force model, much higher hot air entrainment and higher server inlet temperatures were predicted as compared to the porous jump model. Even when the rack air flow requirement is matched with the tile air flow supply, considerable hot air recirculation is predicted. With partial containment, where only a curtain at the top of the cold aisle is deployed and side doors are opened, improved cold air delivery is suggested.
Publisher
ASME International
Subject
Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials
Reference14 articles.
1. Schmidt, R., Vallury, A., and Iyengar, M., 2011, “Energy Savings Through Hot and Cold Aisle Containment Configurations for Air Cooled Servers in Data Centers,” Pacific Rim Technical Conference and Exposition on Packaging and Integration of Electronic and Photonic Systems (InterPACK), Portland, OR, July 6–8, ASME Paper No. IPACK2011-52206.10.1115/IPACK2011-52206 2. Shrivastava, S. K., Calder, A. R., and Ibrahim, M., 2012, “Quantitative Comparison of Air Containment Systems,” 13th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), San Diego, CA, May 30–June 1, pp. 68–77.10.1109/ITHERM.2012.6231415 3. Takahashi, M., Uekusa, T., Kishita, M., and Kaneko, H., 2008, “Aisle-Capping Method for Airflow Design in Data Centers,” IEEE 30th International Telecommunications Energy Conference (INTELEC 2008), San Diego, CA, September 14–18.10.1109/INTLEC.2008.4664047 4. Gondipalli, S., Sammakia, B., Bhopte, S., Schmidt, R., Iyengar, M. K., and Murray, B., 2009, “Optimization of Cold Aisle Isolation Designs for a Data Center With Roofs and Doors Using Slits,” Pacific Rim Technical Conference and Exposition on Packaging and Integration of Electronic and Photonic Systems (InterPACK), San Francisco, CA, July 19–23, ASME Paper No. InterPACK2009-89203.10.1115/InterPACK2009-89203
Cited by
15 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
|
|