Abstract
To investigate the shear capacity of indirectly loaded reinforced concrete beams under and after fire exposure, load tests were conducted on eight full-scale specimens exposed to fire testing in a furnace chamber, and the effects of additional transverse reinforcement in the junction region between the primary and secondary beams on the shear capacity, fire resistance, failure modes and deflection were analysed. The results indicate that the slopes of the diagonal cracks in post-fire tested reinforced concrete beams without additional transverse reinforcement were shallower than those of a similar reference beam not exposed to fire, and that the ultimate capacities of reinforced concrete beams with additional transverse reinforcement decreased obviously after fire exposure. However, beams with additional transverse reinforcement exhibited increased fire resistance times and reduced strains in their reinforcement, indicating the benefit of conservatively providing such reinforcement. The findings of this study are expected to provide a reference for the improved fire-resistant design of indirectly loaded beams.