Author:
Chandrasekaran K.,Simon Sishaj P.
Abstract
Restructuring of power system changed the mechanism of reliability management in solving the unit commitment problem (UCP). In general, operating reserve capacity is predetermined either by dispatch rules or predefined by reliability index. This paper considers that the operating reserve capacity in a power system is bendable, which is based on the cost-reliability issues. In UCP, these two competing objectives such as fuel cost and reliability level of the system were optimized simultaneously, as a multi-objective unit commitment problem (MOUCP), using the proposed fuzzy integrated binary real coded cuckoo search Lagrangian (BCSL) algorithm. The ON/OFF status of the thermal power units is obtained by binary coded cuckoo search algorithm (CSA), where as the economic dispatch is obtained by Lagrangian multiplier method. The fuzzy set theory is used to pick up the best compromise solution. The proposed methodology is tested and validated for both the single and multi-objective UCP. The effectiveness of the proposed technique is demonstrated on IEEE RTS 24 bus system by comparing its performance with other methods reported in the literature.Keywords: binary coded cuckoo search algorithm, fuzzy set theory, reliability index, reserve scheduling, unit commitment problem.
Publisher
African Journals Online (AJOL)
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献