Comparison between Different Electrical Configurations of Emergency Diesel Generators for Redundancy and Reliability Improving
-
Published:2018-11-30
Issue:4
Volume:62
Page:144-148
-
ISSN:2064-5279
-
Container-title:Periodica Polytechnica Electrical Engineering and Computer Science
-
language:
-
Short-container-title:Period. Polytech. Elec. Eng. Comp. Sci.
Author:
Elia Stefano,Santini Ezio,Tobia Manuel
Abstract
The failure of an emergency diesel generator could cause a blackout with economic or human losses, especially if it occurs in a hospital. The authors performed an up to date statistic on diesel generators fails has been investigated in a hundred of hospitals. Although standard maintenance operation has been correctly performed, it has been found a 6 % of failures for the genset per year. MTBF of generators and main components have been investigated and updated values are reported in this paper. Components reliability is proved to be at its maximum technological value, consequently an innovative solution is here proposed. Often neighboring buildings or different electrical systems have separated emergency generators. Nowadays, in case of genset failure, most of the electrical installations are not designed to be fed from other generators. Several electrical configurations for diesel generators interconnections have been studied, in order to guarantee the mutual succor between them and therefore improving reliability. Two innovative schemes for emergency generators connection are here proposed for a more reliable electrical design.
Publisher
Periodica Polytechnica Budapest University of Technology and Economics
Subject
Electrical and Electronic Engineering,Computer Networks and Communications,Computer Science Applications,Information Systems,Signal Processing,Software
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献