Abstract
The demand for a low voltage direct current (LVDC) microgrid is increasing by the increase of DC-based digital loads and renewable resources and the rapid development of power electronics technology. For the stable operation of an LVDC microgrid, it is necessary to develop a protection method. In this paper, the new protection scheme considering the fault section is proposed using wavelet transform (WT) in an LVDC microgrid. The fault sections are classified into DC side of the alternating current (AC)/DC converter, DC/DC converter connected to photovoltaic (PV) system, DC line, and DC bus. The characteristics of fault current at each fault section are analyzed. Based on these analyses, the new protection scheme including the fault section estimation is proposed using WT. The proposed scheme estimates the fault section using the detail component after performing WT and sends the trip signal to each circuit breaker according to the fault section. The proposed protection scheme is verified through various simulations according to the fault region and fault current using electromagnetic transient program (EMTP)/ATPDraw and MATLAB. The simulation results show that the fault section is accurately determined, and the corresponding circuit breaker (CB) operations are performed.
Funder
Yonam Institute of Technology
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
12 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献