Affiliation:
1. Irkutsk National Research Technical University
Abstract
THE PURPOSE. This paper considers the problem of relay protection functioning when the current transformer reaches the saturation mode which is provided by transient processes.METHODS. MATLAB Simulink software environment allows reproducing the method of statespace representation by using structural blocks. The model is verified by comparison the time to saturation, obtained by calculation and according to the graphical data of the model. The separation of variables method extracts and graphically displays the investigated components.RESULTS. This paper reveals that applying the requirements of IEC 61869-2:2012 standard, which determines the worst combination of series of unfavorable factors for current transformers in transient mode, can influence a serious impact on the correct operation of relay protection based on current, reactance or differential principle of action. Saturation of the current transformer can lead to both negative results: false operation of relay protection devices and their failure.CONCLUSION. According to the results of the study, it was determined that the presence of a DC component in the primary short-circuit current has the greatest effect on the protection operation. The delays in the restoration of the RMS value of the short-circuit current reached up to 0.3 seconds, which is comparable with the response time of the second protection zones for microprocessor-based relay protection devices. The DC component of the primary current and the presence of residual magnetic induction of the current transformer provides the largest content of the magnetization current, the largest angular error and also the largest content of the second harmonic component in the secondary short-circuit current.
Publisher
Kazan State Power Engineering University
Subject
Pharmacology (medical),Complementary and alternative medicine,Pharmaceutical Science
Reference17 articles.
1. Dragan Ristanovic, Terry Tadlock, Gautami Bhatt, Current Transformers in Protection Applications: The ANSI and International Electrotechnical Commission Standards, Industry Applications journal. IEEE. 2021;27(5):47-57.
2. Rumiantsev YuV, Romaniuk FA, Rumiantsev VYu, et al. Digital Current Measurement Element for Operation During Current Transformer Severe Saturation. ENERGETIKA. Proceedings of CIS higher education institutions and power engineering associations. 2018;61(6):483-493. https://doi.org/10.21122/1029-7448-2018-61-6-483-493
3. Dmitriev MV and Evdokunin GA. Modeling transient processes in an electric grid containing transformers when taking account of the configuration of their magnetic system. Izv. RAN. Énergetika.2009;2:37-48.
4. Naseri F, Kazemi Z, Arefi MM. Fast discrimination of transformer magnetizing current from internal faults: An extended Kalman filter-based approach. IEEE Trans. Power Del. 2018;33(1):110-118.
5. Bagenov NG, Antipanova IS. The mathematical description of electromagnetic processes in the transformers. Power engineering: research, equipment, technology. 2015;(1-2):107-114. https://doi.org/10.30724/1998-9903-2015-0-1-2-107-114
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献