Author:
Edelstein P H,Whittaker R E,Kreiling R L,Howell C L
Abstract
The effect of ozonation of supply water for one wing of an unoccupied hospital building which had positive cultures for Legionella pneumophila from multiple potable water fixtures was studied in a prospective, controlled fashion. Mean ozone residual concentrations of 0.79 mg/liter eradicated L. pneumophila from the fixtures, but so did nonozonated water in the control wing fixtures. The efficacy of the nonozonated water was most probably due to a mechanical flushing effect and to an unexpected rise in the chlorine content of the supply water. Determination of the in vitro activity of ozone against L. pneumophila did not predict the efficacy of its eradication from water fixtures treated with ozone.
Publisher
American Society for Microbiology
Subject
Ecology,Applied Microbiology and Biotechnology,Food Science,Biotechnology
Reference13 articles.
1. Anhalt J. P. L. D. Sabath and A. L. Barry. 1980. Special tests: bactericidal activity activity of antimicrobics in combination and detection of 3-lactamase production p. 478-484. In E. H. Lennette A. Balows W. J. Hausler Jr. and J. P. Truant (ed.) Manual of clinical microbiology 3rd ed. American Society for Microbiology Washington D.C.
2. An improved semiselective medium for the isolation of Legionella pneumophila from contaminated clinical and environmental specimens;Edelstein P. H.;J. Clin. Microbiol.,1981
3. Edelatein P. H. J. B. Snitzer and S. M. Finegold. 1982. Isolation of Legionella pneumophila from hospital potable
4. 1334 EDELSTEIN ET AL.
5. Failure of Legionella pneumophila sensitivities to predict culture results from disinfectant-treated air-conditioning cooling towers;England A. C.;AppI. Environ. Microbiol.,1982
Cited by
57 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献