Author:
England A C,Fraser D W,Mallison G F,Mackel D C,Skaliy P,Gorman G W
Abstract
The disinfection of cooling towers based on manufacturers' treatment protocols, as employed in units installed at various public gathering places in Dallas, Tex. (hotels, municipal auditorium), and at the city health department, was evaluated for effectiveness in controlling Legionella pneumophila and compared with previous laboratory studies. In specimens collected in September and December, 1978, L. pneumophila was isolated from 2 of 4 specimens from untreated cooling towers, 2 of 4 specimens from towers treated with agents deemed ineffective in earlier laboratory tests, 6 of 11 specimens from towers treated with putatively effective agents, and 0 of 4 specimens from towers treated with an agent unknown efficacy. These results suggest the need for further studies to identify biocidal agents effective in eliminating L. pneumophila from air-conditioning cooling towers.
Publisher
American Society for Microbiology
Subject
Ecology,Applied Microbiology and Biotechnology,Food Science,Biotechnology
Cited by
45 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献