Affiliation:
1. State Grid Shanxi Electric Power Company Maintenance Branch, Taiyuan 030032, China
2. State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an 710049, China
Abstract
Under working conditions, the conductive rods in the GIS flow through the power frequency alternating current. Due to the coupling effect of the magnetic field and electric field between the metal aluminum shell and the conductive rod, induced eddy currents are generated in the metal
shell of the GIS. The heat generated by the current heating effect of the GIS conductive rod and the eddy current loss of the metal casing will cause the temperature rise of GIS equipment. Due to the limited volume, the heat dissipation capacity of GIS is poor. Excessive temperature rise will
accelerate the insulation aging of GIS equipment, and even damage its insulation, which will affect safe operation. In order to obtain the temperature change law of GIS, related influencing factors such as eddy current loss, skin effect, proximity effect, convective heat transfer of SF6
gas, and gravity of SF6 gas are comprehensively considered. The finite element analysis is used to research and discuss GIS magnetic field distribution, eddy current, temperature distribution and SF6 gas velocity. The initial value of the temperature of each part is set
to 293.15 K (20 °C), and the temperature in the GIS is calculated to gradually decrease from the inside to the outside under the rated AC current of 3150 A. The temperature at the conductive rod position is the highest at 335.32 K, and the temperature at the housing position is the lowest
at 294.65 K.
Publisher
American Scientific Publishers
Subject
Electrical and Electronic Engineering,Electronic, Optical and Magnetic Materials
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献