Abstract
The purpose of this study is to report the experience of the implementation and application of a 3-year Water Safety Plan (WSP) together with the secondary disinfection of water by monochloramine to control and prevent healthcare-associated legionellosis in an Italian hospital strongly colonized by Legionella. Risk assessment was carried out by the WSP team. The main critical control points focused on in developing the WSP for the control of Legionella was the water distribution system. A sampling plan for the detection of Legionella was implemented. A widespread contamination of the hot water distribution system by L. pneumophila sg5 was found. Results after 3 years of the continuous disinfection of hot water with monochloramine indicate the eradication of Legionella. The implementation and application of a WSP in a hospital, together with the disinfection of the water distribution system with monochloramine, can be effective in controlling the growth of Legionella and in preventing nosocomial legionellosis.