Abstract
The CLP (containment liner plate) of a nuclear power plant protects the internal system from the external environment and sudden changes in internal pressure or temperature, and it is a structure that blocks and protects radioactive materials leaking inside and outside in the event of a nuclear accident and is composed of a liner plate, reinforcing bars, tendons, and concrete. Recently, corrosion on the rear side of the liner plate and concrete voids has emerged as a severe defect in nuclear power plants across South Korea. Therefore, in this study, we proposed a new inspection method that a line-type inspection method applied phased array ultrasonic testing and the area inspection method applied acoustic resonance method using developed moveable tapper. The acoustic signals were signal-processed and reproduced to a mapping image following the inspection area, and with the image, it was possible to determine the type of defect. Furthermore, an automated inspection system for within the CLP was proposed.
Funder
Korea Institute of Energy Technology Evaluation and Planning
Subject
General Materials Science
Reference23 articles.
1. Development of inspection technique for filling or unfilling of containment liner plate backside concrete in nuclear power plant;Lee;Trans. Korean. Soc. Press. Vessel. Pip.,2020
2. Present status of nuclear containments and ISI in Korea
3. Characteristics of Earthquake Responses of and Isolated Containment Building in Nuclear Power Plants According to Natural Frequency of Solid;Lee;J. Earthquake Eng.,2013
4. A Study on the Nondestructive Evaluation Method for Detecting Void in Containment Liner Plate
Cited by
7 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献