Nömm Jakob,Rönnberg Sarah,Bollen Math
Abstract
Voltage quality data has been collected in a single house nanogrid during 48 weeks of islanded operation and 54 weeks of grid-connected operation. The voltage quality data contains the voltage total harmonic distortion (THD), odd harmonics 3 to 11 and 15, even harmonics 4 to 8, voltage unbalance, short-term flicker severity (Pst) and long-term flicker severity (Plt) values, and voltage variations at timescales below 10 min. A comparison between islanded and grid-connected operation values was made, were some of the parameters were compared to relevant grid standard limits. It is shown that some parameters exceed the defined limits in the grid-standards during islanded operation. It was also found that the islanded operation has two modes of operation, one in which higher values of the short circuit impedance, individual harmonic impedance, harmonic voltage distortion and voltage unbalance were reached.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Reference17 articles.
1. Microgrids Architectures and Control;Hatziargyriou,2014
2. Microgrids
3. Microgrids 1: Engineering, Economics, & Experience,2015
4. A review of nanogrid topologies and technologies
5. Voltage Characteristics of Electricity Supplied by Public Electricity Networks,2010