Affiliation:
1. Institute of Numerical Modelling, University of Latvia, Jelgavas Street 3, LV-1004 Riga, Latvia
Abstract
For an efficient indoor air purification, it is important to know the detailed airflow distribution in the room. A series of numerical simulations are carried out for five heating regimes using an air–air heat pump, capillary mat on the ceiling, capillary mat on the walls, heated floor, and radiator. The most homogeneous temperature field is obtained for the case with the heated floor. The highest velocity is obtained for the air–air heat pump, while the lowest is obtained for the capillary mat on the ceiling. A portable air cleaner based on the prototype device is introduced into the model and its influence on the velocity and temperature distributions is calculated. Our simulations additionally consider is the transport of an infectious aerosol and its purification inside the air cleaner. The time dependency of the concentration is exponential, and the purification rate depends on the air cleaner’s orientation and heating regime. The efficiency is higher for a purifier with flow in the upwards direction compared to in a horizontal one. In the experimental part, an NaCl solution is dispersed into the air, and the efficiency of purification in the case of the air–air heat pump is evaluated by measuring the time-dependent particle concentrations. These experimental results corroborate the numerical model.
Funder
European Regional Development Fund
REACT-EU funding
Subject
Atmospheric Science,Environmental Science (miscellaneous)
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献