Abstract
A large number of bubbles generated by the air agitation device in an external melting ice storage system can cause the disturbance of the ice–water mixture, which can enhance the heat transfer and contribute to the reduction in energy consumption. The structural design and optimization of the air agitation device in an external melting ice storage system is the key issue for energy savings. In this study, the influence of different orifice spacings and diameters on the distribution of the gas–liquid flow field, gas holdup, heat-transfer coefficient, and power consumption in the ice storage tank was investigated by numerical simulation. The simulated results showed that the heat-transfer coefficient of the ice–water mixture with air bubbles should be 3–5 times higher than the natural convection when the air superficial velocity is 0.03 m/s. The gas holdup was mainly affected by the orifice spacing, and the maximum varied from 5.0% to 8.2%. When the orifice spacing was less than 150 mm, the gas holdup changed a little in the horizontal direction, and the uniformity became worse when the orifice spacing was larger than 180 mm. An orifice diameter larger than 3 mm can improve the heat transfer and cause less air-compressing energy consumption, which decreased by approximately 1.62%.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction