Cooling Effectiveness of a Data Center Room under Overhead Airflow via Entropy Generation Assessment in Transient Scenarios

Author:

Silva-Llanca Luis,del Valle Marcelo,Ortega Alfonso,Díaz Andrés

Abstract

Forecasting data center cooling demand remains a primary thermal management challenge in an increasingly larger global energy-consuming industry. This paper proposes a dynamic modeling approach to evaluate two different strategies for delivering cold air into a data center room. The common cooling method provides air through perforated floor tiles by means of a centralized distribution system, hindering flow management at the aisle level. We propose an idealized system such that five overhead heat exchangers are located above the aisle and handle the entire server cooling demand. In one case, the overhead heat exchangers force the airflow downwards into the aisle (Overhead Downward Flow (ODF)); in the other case, the flow is forced to move upwards (Overhead Upward Flow (OUF)). A complete fluid dynamic, heat transfer, and thermodynamic analysis is proposed to model the system’s thermal performance under both steady state and transient conditions. Inside the servers and heat exchangers, the flow and heat transfer processes are modeled using a set of differential equations solved in MATLAB™. This solution is coupled with ANSYS-Fluent™, which computes the three-dimensional velocity, temperature, and turbulence on the Airside. The two approaches proposed (ODF and OUF) are evaluated and compared by estimating their cooling effectiveness and the local Entropy Generation. The latter allows identifying the zones within the room responsible for increasing the inefficiencies (irreversibilities) of the system. Both approaches demonstrated similar performance, with a small advantage shown by OUF. The results of this investigation demonstrated a promising approach of data center on-demand cooling scenarios.

Funder

National Science Foundation

Comisión Nacional de Investigación Científica y Tecnológica

Publisher

MDPI AG

Subject

General Physics and Astronomy

Reference24 articles.

1. Comparison of Overhead and Underfloor Air Delivery Systems in a Data Center Environment Using CFD Modeling;Sorell;ASHRAE Trans.,2005

2. Measurements and predictions of the air distribution systems in high compute density (Internet) data centers

Cited by 17 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. Data centers cooling: A critical review of techniques, challenges, and energy saving solutions;International Journal of Refrigeration;2024-04

2. Evaporative cooling method to improve energy management of overhead downward flow-type data center;Case Studies in Thermal Engineering;2023-05

3. The immersion cooling technology: Current and future development in energy saving;Alexandria Engineering Journal;2022-12

4. Research on Air-conditioning Operation Energy Saving in Internet Data Center;2022 8th International Conference on Hydraulic and Civil Engineering: Deep Space Intelligent Development and Utilization Forum (ICHCE);2022-11-25

5. Numerical Study for Flow Loss Characteristic of an Axial-Flow Pump as Turbine via Entropy Production Analysis;Processes;2022-08-26