Analysis of a High-Voltage Room Quasi-Smoke Gas Explosion

Author:

Bakka Marit Sigfrid,Handal Erling Kristian,Log TorgrimORCID

Abstract

During an air separation unit shut-down in a methanol production plant, a stop signal was sent to the control cabinet of a synchronous motor for a booster compressor. The control cabinet stopped magnetizing the rotor, while the system logic ensured that the power circuit breakers for the start reactor coils were opened, in order to be ready for the next start-up. Unintentionally, the circuit breaker was still connected (i.e., power was let through the reactors for a prolonged time period), which led to extensive overheating. Subsequently, the central control room received an unaddressed sub-station smoke alarm, and plant operators were sent out to locate the possible source of smoke. The accessible rooms were searched, and traces of smoke were confirmed. The Emergency Response Organization (ERO) was mustered and, through inspection, the Emergency Response Team (ERT) realized that the smoke originated from a ground floor high-voltage room. Fire hoses were arranged for fire extinguishing, and the ERT withdrew to wait for the room to be electrically isolated. About one minute after briefly opening the only set of doors to the high-voltage room, flames were observed, and a quasi-smoke gas explosion violently forced both door blades open and released a substantial fire ball. Personnel had been in the risk zone shortly before the explosion, but luckily no personnel were hit by the slamming door blades or the emerging flames. The incident revealed several learning points related to improper maintenance, ambiguous smoke alarm, lack of flame detectors in the high-voltage room, insufficient risk understanding and training regarding electrically related fire incidents, and the absence of an automatic fire suppression system. In plants processing hydrocarbons, the safety focus regarding hydrocarbon fire and explosion risk is paramount. However, risks related to electrical accidents and compartment fire dynamics (e.g., backdraft and smoke gas explosion) should also be given proper attention.

Publisher

MDPI AG

Subject

Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)

Cited by 2 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3