Abstract
To prevent the frequent occurrence of transmission line galloping accidents, many scholars have carried out studies. However, there are still many difficulties that have not been solved. To address the issues that have arisen during the installation of the monitoring system, a new installation technique for the galloping monitoring terminal structure has been developed, and structural design and transmission line impact have been taken into account. A method combining Kalman and Mahony complementary filtering has been shown to solve the problem of wire twisting when galloping is taken into account. The displacement is derived by double-integrating the acceleration, although the trend term has a significant impact on the integration result. To handle the trend term issue and other error effects, a method combining the least-squares method, the adaptive smoothing method, and the time-frequency domain hybrid integration approach is used. Finally, the monitoring terminal’s structural design is simulated and evaluated, and the measured amplitude is assessed on a galloping standard test bench. The difference between the measured amplitude and the laboratory standard value is less than 10%, meeting the engineering design criteria. And the galloping trajectory is identical to the test bench trajectory, which is critical for user end monitoring.
Funder
the National Natural Science Foundation of China Youth Fund
Subject
Electrical and Electronic Engineering,Biochemistry,Instrumentation,Atomic and Molecular Physics, and Optics,Analytical Chemistry
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献