Affiliation:
1. School of Civil Engineering, Taiyuan University of Technology, Taiyuan 030024, China
Abstract
In practice, the outflow from a diffuser is highly non-uniform due to many reasons. However, the air outflow velocity from a diffuser is uniform in most current studies. Little research has been conducted to determine under what conditions uniform velocity can be used. Therefore, based on the non-uniformity of velocity, airflow characteristics of grille and ceiling diffusers were investigated experimentally and numerically. Two generic CFD cases (non-uniform and uniform velocity) are presented. The velocity field near the diffuser is investigated with measurements in order to determine velocity-inlet boundary conditions. The study shows that the uniform velocity-inlet boundary condition can be considered accurate only under certain conditions. For the grille diffuser, the aspect ratio affects the distribution of the outflow velocity. Using uniform velocity as the velocity-inlet boundary condition for the grille diffuser would result in at least a 14.2% error in the jet region, except when the outflow aspect ratio is 1 and the average velocity is greater than 1.83 m/s. However, when the average velocity of the ceiling diffuser is 3.64 m/s, the error of using uniform velocity as the velocity-inlet boundary condition reaches 58.3%. This study provides the basis for determining the velocity-inlet boundary conditions during numerical simulations.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Reference37 articles.
1. Zhu, H.-C., and Cao, S.-J. (2020). Building Simulation, Tsinghua University Press.
2. A numerical airflow pattern study of a floor swirl diffuser for UFAD system;Yau;Energy Build.,2018
3. Local attachment ventilation system for the unearthed relic preservation area within site museum;Dang;Sustain. Cities Soc.,2022
4. (2006). Ergonomics of the Thermal Environment—Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria (Standard No. ISO 7730:2005).
5. (2004). Thermal Environmental Conditions for Human Occupancy (Standard No. ANSI/ASHRAE Standard 55-2004).
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献