The research on the particle concentration distribution of directed airflow in cleanrooms for operators

Author:

Li Chao,Li Hao,Zhang Minwei,Wang XinORCID,Huang Cui

Abstract

Existing research of non-unidirectional cleanrooms generally suggests that lower-side return air outlets provide better control effect on indoor particle concentration. As a result, there has been relatively less focus on return air outlets. However, installing return air outlets oriented towards operators as particle emission sources can reduce the impact on process layout and improve space utilization, while also provide less impact from upper particle emission sources on the workbench area. To investigate the characteristics of return air outlet for operators (abbreviated as H), this study compared the particle concentration distribution, non—uniformity, and purification efficiency of return air oultet H and the traditional lower-side (abbreviated as L) return air outlets by experiments and CFD simulations. Based on the theory of mass conservation, the expression of required air supply volume under equivalent cleanroom conditions was derived. Under corresponding experimental and simulation conditions, the particle concentration differences range from 2.0% to 12.7% for return air outlet H and from 12.4% to 33.2% for return air outlet L, and these differences gradually decrease with the air exchange rate (ACH) increases. The results show that ACH = 20 is sufficient for cleanliness requirements with return air outlet H when there is one person in the cleanroom, while a higher rate of ACH = 35 is needed when there are two persons. Although lower-side return air outlets have certain potential for reducing particle concentration in the cleanroom, increasing the air exchange rate remains the most effective method to control indoor particle concentration. Compared to the traditional lower-side return air outlet L, the ranges of the non-uniformity coefficients for return air outlet H and L are 0.50 to 0.67 and 0.45 to 0.53, respectively. The average non-uniformity coefficient differs by 11.9%, and there is not a significant difference in uniformity with more than 20 air changes per hour. The use of return air outlets H only requires an additional 11% of air supply volume to achieve the same cleanliness, demonstrating its effectiveness in controlling particle concentration. It is suitable for cleanrooms with higher requirements for workbenches and for cleanrooms with restricted floor usage or requiring flexible layouts. The study also explores the impact of width of return air outlet oriented towards operators as particle emission sources, the results show that the larger-sized outlets facilitate the particle discharge and control the particle distribution inside the room.

Publisher

Public Library of Science (PLoS)

Reference41 articles.

1. Energy performance and energy conservation technologies for high-tech cleanrooms: State of the art and future perspectives;W Zhao;Renewable and Sustainable Energy Reviews,2023

2. Clean room industry development and demand report. Huaon Industrial Research Institute. 2021.

3. P M. An estimate of energy use in laboratories, cleanrooms, and data centers in New York. Lawrence Berkeley National Laboratory. 2008: 4–6.

4. Dynamic emission rates of human activity in biological cleanrooms;F Zhang;Building and Environment,2022

5. Experimental investigation into cleanroom contamination build-up when applying reduced ventilation and pressure hierarchy conditions as part of demand controlled filtration;MGLC Loomans;Building and Environment,2020