Author:
Owens John,Xiao Ang,Bonk Jason,DeLorme Michael,Zhang Agnes
Abstract
For many years, SF6 has been the preferred dielectric medium in electrical power applications, particularly in high voltage gas-insulated equipment. However, with the recognition that SF6 has an extremely long atmospheric lifetime and very high global warming potential, governments have pursued emission reductions from gas-filled equipment. The electrical power industry has responded to this environmental challenge applying SF6-free technologies to an expanding range of applications which have traditionally used SF6, including gas-insulated switchgear, gas-insulated circuit breakers and gas-insulated lines or bus bars. Some of these SF6-free solutions include gas mixtures containing fluorinated compounds that have low climate impact, among them, a fluoronitrile and a fluoroketone developed as 3M™ Novec™ 4710 Insulating Gas and 3M™ Novec™ 5110 Insulating Gas, respectively. Both fluoronitrile and fluoroketone mixtures are successfully used in gas-insulated equipment currently operating on the grid where they reduce greenhouse gas emissions by more than 99% versus SF6. This paper reviews these leading components of alternative-gas mixtures with updates on the performance, safety and environmental profiles in electrical power applications.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
26 articles.
订阅此论文施引文献