Elimination of the Impact Produced by DG Units on the Voltage Profile of Distribution Networks

Author:

Ouali Saad1ORCID,Cherkaoui Abdeljabbar1

Affiliation:

1. Laboratory of Innovative Technologies (LTI), National School of Applied Sciences, Abdelmalek Essaadi University, Tangier, Morocco

Abstract

In this paper, an alternative strategy for real-time control of active distribution network voltage is developed, not by controlling the bus voltage as in the various centralized, decentralized, and local approaches presented in literature but rather by only eliminating the impact produced by active and reactive power of distributed generation (DG) units on the voltage of all network nodes and keeping the traditional voltage control systems dealing with the same constraints of passive systems. In literature, voltage deterioration introduced by DGs has been reported as one of the main obstacles for the interconnection of large amounts of DG units to the existing networks. In this paper, the novel control strategy is based on a sensitivity formula developed to calculate the compensation needed for additional distributed flexible AC transmission system (D-FACTS) devices to push and pull the exact reactive power and to eliminate the impact produced by DGs on the network voltage profile. The criteria of the allocation of the var devices and the required network reinforcement are developed in this paper, considering all possible topology structures, and an innovative codification method is introduced to reduce the needed computation time and communication data to actualize the sensitivity coefficients and get the proposed control approach flexible with network topology reconfiguration. The risk of the conflict of the proposed control system with the traditional voltage equipment is reduced due to the fast capability of D-FACTS devices to regulate their reactive power in finer granularity. A case study of two meshed IEEE 15-bus feeders is introduced to compare the voltage behavior with and without the presence of DG units and to evaluate the total system losses. The proposed method could be used for the interconnection of the first generation units in emerging networks, which does not yet have an active voltage control strategy, as it could be used for DG units not able to be connected to existing centralized control systems and it could also be used as the principal voltage control strategy, with the extension for several neighboring units and the preservation of the traditional voltage control systems.

Publisher

Hindawi Limited

Subject

Applied Mathematics

Cited by 3 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3