Affiliation:
1. School of Power and Mechanical Engineering, Department of Automation, Wuhan University, Wuhan 430072, China
Abstract
For the operation of the supercritical once-through boiler generation units, the control of the temperature at intermediate point (IPT) is highly significant. IPT is the steam temperature at the outlet of the separator. Currently, PID control algorithms are widely adopted for the IPT control. However, PID cannot achieve the optimal performances as the units’ dynamic characteristic changes at different working points due to the severe nonlinearity. To address the problem, a new control algorithm using affine nonlinear system is adopted for a 600 MW unit in this paper. In order to establish the model of IPT via affine nonlinear system, the simplified mechanism equations on the evaporation zone and steam separator of the unit are established. Then, the feedback linearizing control law can be obtained. Full range simulations with the load varying from 100% to 30% are conducted. To verify the effectiveness of the proposed control algorithm, the performance of the new method is compared with the results of the PID control. The feed-water flow disturbances are considered in simulations of both of the two control methods. The comparison shows the new method has a better performance with a quicker response time and a smaller overshoot, which demonstrates the potential improvement for the supercritical once-through boiler generation unit control.
Funder
National Key Technology R&D Program of China
Subject
General Engineering,General Mathematics
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献