Study on Energy Efficient Operation of Air-Conditioning Cooling Water System

Author:

Liang Wang,Lu-lu Yang,Ya-bin Tian

Abstract

The control logic of frequency adjustment for pump and cooling tower fan has been presented in this paper, based on the operation mode of a chiller with one pump and one cooling tower. Optimum outlet water temperature control of cooing tower has been put forward through analysis and comparison among factors influencing it, based on measured data. A mathematical model of energy consumption has been established under different outdoor wet-bulb temperature and load rate conditions. The optimized controlling strategy has been obtained after the analysis on energy consumption under two different operational strategies with different number of cooling towers in service. In partial load condition, the best operation mode of cooling water system is the optimal water outlet temperature control system, which aims at the lowest comprehensive system energy consumption. Cooling water system can match the best temperature difference and determine the fan frequency according to optimum outlet temperature automatically. Variable frequency control should be applied to fans; meanwhile, routing maintenance and cleaning is also needed for an even distribution of water and effective use of heat exchange area.

Publisher

Bentham Science Publishers Ltd.

Subject

Electrical and Electronic Engineering

Cited by 1 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3