Some Factors in the Design of Surface Condensing Plant

Author:

Guy H. L.1,Winstanley E. V.2

Affiliation:

1. Mechanical Department, Metropolitan - Vickers Electrical Company.

2. Mechanical Department, Metropolitan-Vickers Electrical Company.

Abstract

It is suggested that the poor performance of certain large surface condensers is due to pressure drop on the steam side. Tests are given showing the pressure drop for various patterns of tube plates and illustrating the steps taken to reduce it. The effect of pressure drop upon the mean temperature difference is discussed. The limitations of accepted formulae are criticized and the results of more accurate analysis are presented. The results of Eagle and Ferguson's tests on heat transmission from tube to water are presented in terms of the external surface for the range of normal condensing plant. Utilizing these results, the overall rates of heat transmission from a large number of tests on commercial condensers are analysed in order to obtain the rate of heat transmission from steam to tube, and after a discussion of the results a mean value is suggested. A set of curves of overall rates of heat transmission on this basis is presented as applicable to brushed tubes. A method of obtaining the net heat rejected to the circulating water in power plant is developed and the departure from the conventional figure of 1,000 B.Th.U. per lb. is brought out. The results obtained on a series of tests on individual tubes in a complete condenser are analysed and commented upon. The paper also deals with the effect of tube fouling upon the overall rate of heat transmission, and methods of obtaining a margin in surface to allow for this are discussed. The effect of pressure drop upon the duty of an air extraction plant and certain problems arising therewith are discussed. Some actual air leakage tests are given and compared with recognized standard allowances. The authors deal with the friction on the water side of condensers and give test figures of the friction in the tube with various methods of tube plate fastenings. Recommended standard values of the various factors for assessing condenser water friction are given, together with tests from commercial installations. The paper concludes with a treatment of the problem of syphonic return in condenser circulating water systems and gives a method of calculating the syphonic efficiency.

Publisher

SAGE Publications

Subject

General Engineering

Cited by 13 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. Pressure drop measurements in a low pressure steam condenser with a horizontal bundle of staggered tubes;Applied Thermal Engineering;2004-06

2. Henry Lewis Guy, F. R. S., 1887-1956, Turbine designer and engineering administrator;Notes and Records of the Royal Society of London;1966-12-31

3. Hydraulic Design of Syphons;Proceedings of the Institution of Mechanical Engineers;1965-06

4. Inlet and outlet losses of condenser tubes;Applied Scientific Research;1965

5. Determination of the Optimum Level of a Steam Power Station Turbine House from Hydraulic and Constructional Considerations;Proceedings of the Institution of Mechanical Engineers;1963-06

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3