A 16-month study was conducted on the presence of Aeromonas hydrophila in drinking water in Indiana, U.S.A. Enumeration was conducted in source water, in various sites within a water treatment plant, and in the distribution system in both bulk water and biofilm, as well as in a simulated (annular reactors) drinking-water distribution system. Presumptive Aeromonas spp. counts on source waters regularly approached 103104CFU/100 mL, during summer months and granular activated carbon - filtered water counts ranged from <1 to 490 CFU/100 mL. In source water, presumptive Aeromonas levels were related to water temperature. Aeromonas hydrophila was never detected in the treatment plant effluent or distributed bulk water, showing disinfectant efficiency on suspended bacteria; however, isolates of A. hydrophila were identified in 7.7% of the biofilm samples, indicating a potential for regrowth and contamination of drinking-water distribution systems.Key words: Aeromonas hydrophila, distribution system, biofilm.