Author:
Setyawan Andriyanto,Najmudin Hafid,Badarudin Apip,Sunardi Cecep
Abstract
An experimental investigation on the performance of an air conditioner and its operating conditions under constant outdoor moisture content and varied dry-bulb temperature has been accomplished. The test was conducted on an air conditioner using R32 with a nominal cooling capacity of 2.6 kW and the test was carried out in a controlled and standardized test room. During the test, the outdoor temperature was varied from 24 to 36℃ while maintaining the humidity ratio at 14.9 kg vapor per 1 kg of dry air. The indoor compartment was maintained at 27℃ dry-bulb temperature and 19℃ wet-bulb temperature. Generally, as the temperature of outdoor air increases by 1℃, the input power increases by 1.4%, the cooling capacity decreases by 0.9%, and the coefficient of performance decreases by 1.95%. In addition, the outdoor air temperature has a more significant effect on the refrigerant discharge and liquid line temperature than that of refrigerant suction temperature.
Publisher
International Information and Engineering Technology Association
Subject
Fluid Flow and Transfer Processes,Mechanical Engineering,Condensed Matter Physics