Affiliation:
1. School of Energy and Environment, Zhongyuan University of Technology, Zhengzhou, China
Abstract
For the problems of high compressor discharge temperature and system
performance decay during the operation of cold storage, a parallel flow
heat exchanger based low pressure make-up gas refrigeration system
experimental bench was designed and built, and the changes of refrigeration
system performance were analyzed under different compressor speeds. The
results show that when the compressor speed increases from 2500 rpm to 4500
rpm, the compressor discharge temperature increases, the refrigeration
capacity increases by 39.53% and the compressor power increases by 38.89%,
in addition, as the speed increases, the system COP shows a trend of first
increasing and then decreasing, with the best value of 2.71 at 3500 rpm.
Publisher
National Library of Serbia
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献