In order to understand the energy-saving system of building cooling and
heating integration, the author proposes a research on an energy-saving
system of building cooling and heating integration based on building
information modelling (BIM) technology. The author first analyzed the
energy-saving performance of the system by establishing models for each
module based on meteorological data simulated on the DeST software platform.
Secondly, in order to analyze the energy consumption of the integrated
system, it is necessary to establish a residential building model, and
select the building model in the cold winter and hot summer areas of a city
for analysis. The results show that due to the system?s heat storage
function, there is no need to consume electricity in spring and autumn.
Compared to the electric heating hot water mode, the integrated system can
save 1198.85 kWh of electricity in non-cooling and heating seasons, with a
100% energy-saving rate. Compared to not using an integrated system, it can
achieve an energy-saving rate of 81.9% throughout the entire refrigeration
and heating season, with significant energy-saving effects. The integrated
heating, cooling and hot water system of BIM technology adopts the
technology of cool storage and heat storage coupled with solar energy and
heat pump technology. The system has simple structure, obvious energy-saving
effect, good environmental protection, and can adapt to various climates
throughout the year. The introduction of underfloor heating also increases
the comfort of buildings and residences.