Affiliation:
1. Department of Electrical Engineering Iran University of Science and Technology Tehran Iran
Abstract
AbstractPower outages can cause harm to both society and individual health. Among the crucial elements of power systems, power transformers play a vital role, and their failures can lead to incidents and disruptions. According to statistics, almost 50% of the explosions and fires in the power transformer are caused by oil‐impregnated paper (OIP) bushing failures. Moreover, moisture is a crucial factor that affects the health of OIP bushings, and assessing the moisture level in OIP bushings is vital to guarantee the safety of power systems. While the frequency‐domain dielectric spectroscopy (FDS) method has been widely used to assess the moisture content of OIP bushings on‐site, it has the disadvantage of requiring a long measurement time. Therefore, a novel technique was proposed in this study that involves measuring the OIP bushing dissipation factor (tanδ) at 1 Hz to estimate the moisture content in a significantly shorter time. Five samples of OIP with various moisture levels have been selected, and an equation based on the OIPs' value of tanδ at 1 Hz was proposed to assess the moisture level of OIP bushings. Furthermore, the validity of the proposed method was successfully verified, proving its precision and time efficiency.
Publisher
Institution of Engineering and Technology (IET)
Subject
Electrical and Electronic Engineering
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献