Bindi M.,Grasso F.,Luchetta A.,Manetti S.,Piccirilli M.C.
Abstract
Abstract
In this paper a new method is developed and described, aimed at the modeling and diagnosis of the joints connecting the ends of two cables on a high voltage electricity pylon. Identifying the anomalous joint behaviour through the line frequency response analysis is the first objective of the work. For this reason, it is necessary to model the whole overhead line with a lumped circuit and studying the joint electrical parameter variation. The problem is approached in multiple steps: modelling, testability analysis of the model, optimal frequency selection, identification of the possible failures. Some simulated cases are included in order to show the potentialities of the method.
Subject
General Physics and Astronomy
Reference17 articles.
1. Computation of transmission line parameters for power flow studies;Monteiro,2005
2. Exploring remote monitoring of degraded compression and bolted joints in HV Power transmission lines;De Paulis;IEEE Transactions On Power Delivery,2016
3. Corrosion detection in steel reinforced aluminum conductor cables;Jaffrey,2014