Abstract
Abstract
In distributed generation (DG) systems, the rate of change of voltage and the rate of change of frequency are the two most common and widely used simple and low-cost passive islanding detection schemes. Unfortunately, these passive islanding detection schemes find limitation for detecting the islandings that cause very small power imbalance. In this paper, an improved passive islanding detection scheme is proposed by using the two newly derived indices from the sequence components of the current signal with the conventional voltage and frequency parameters. The performance of the proposed scheme is tested for numerous islanding and non-islanding cases generated on IEEE Std 399–1997 and IEC microgrid model distribution system integrated with both inverter-interfaced and synchronous DGs through PSCAD/EMTDC. The obtained results confirm the effectiveness of the proposed scheme.