An Overview of the IBM Power 775 Supercomputer Water Cooling System

Author:

Ellsworth Michael J.1,Goth Gary F.2,Zoodsma Randy J.3,Arvelo Amilcar4,Campbell Levi A.5,Anderl William J.6

Affiliation:

1. Senior Technical Staff Member Fellow, ASME Advanced Thermal Laboratory, IBM Corporation, Poughkeepsie, NY 12601

2. Senior Technical Staff Member Thermal Engineering and Technologies, IBM Corporation, Poughkeepsie, NY 12601

3. Senior Engineer Thermal Engineering and Technologies, IBM Corporation, Poughkeepsie, NY 12601

4. Advisory EngineerThermal Engineering and Technologies, IBM Corporation, Poughkeepsie, NY 12601

5. Advisory Engineer Advanced Thermal Laboratory, IBM Corporation, Poughkeepsie, NY 12601

6. Advisory Engineer Mechanical Design and Cooling, Midrange Systems, IBM Corporation, Rochester, MN 55901

Abstract

In 2008 IBM reintroduced water cooling technology into its high performance computing platform, the Power 575 Supercomputing node/system. Water cooled cold plates were used to cool the processor modules which represented about half of the total system (rack) heat load. An air-to-liquid heat exchanger was also mounted in the rear door of the rack to remove a significant fraction of the other half of the rack heat load: the heat load to air. The next generation of this platform, the Power 775 Supercomputing node/system, is a monumental leap forward in computing performance and energy efficiency. The computer node and system were designed from the start with water cooling in mind. The result, a system with greater than 96% of its heat load conducted directly to water, is a system that, together with a rear door heat exchanger, removes 100% of its heat load to water with no requirement for room air conditioning. In addition to the processor, the memory, power conversion, and I/O electronics conduct their heat to water. Included within the framework of the system is a disk storage unit (disc enclosure) containing an interboard air-to-water heat exchanger. This paper will give an overview of the water cooling system featuring the water conditioning unit and rack manifolds. Advances in technology over this system’s predecessor will be highlighted. An overview of the cooling assemblies within the server drawer (i.e., central electronics complex,) the disc enclosure, and the centralized (bulk) power conversion system will also be given. Furthermore, techniques to enhance performance and energy efficiency will also be described.

Publisher

ASME International

Subject

Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials

Reference13 articles.

1. The Evolution of Water Cooling for IBM Large Server Systems: Back to the Future;Ellsworth

2. The Evolution of IBM High Performance Cooling Technology;Simons

3. Thermal Management of Air- and Liquid Cooled Multi-Chip Modules;Bar-Cohen;IEEE Trans. Compon., Hybrids Manuf. Technol.

4. LSI Packaging and Cooling Technologies for Fujitsu VP2000 Series;Kaneko;Fujitsu Sci. Technol. J.

5. Hardware Technology for Fujitsu VP2000 Series;Kaneko;Fujitsu Sci. Technol. J.