New Thermal Management Systems for Data Centers

Author:

Ouchi Mayumi1,Abe Yoshiyuki1,Fukagaya Masato2,Kitagawa Takashi3,Ohta Haruhiko4,Shinmoto Yasuhisa4,Sato Masahide5,Iimura Ken-ichi5

Affiliation:

1. National Institute of Advanced Industrial Science and Technology, Central 2, Umezono 1-1-1, Tsukuba, Ibaraki 305-8568, Japan

2. SOHKi Co., Ltd., Ote-machi, Minato-ku, Nagoya, Aichi 455-0046, Japan

3. Kawamura Electric, Inc., 3-86 Akatsuki-cho, Seto, Aichi 489-0071, Japan

4. Department of Aeronautics and Astronautics, Kyushu University, 744 Motooka, Nishi-ku, Fukuoka 819-0395, Japan

5. Department of Advanced Interdisciplinary Science, Utsunomiya University, 7-1-2 Yoto, Utsunomiya, Tochigi 321-8585, Japan

Abstract

Energy consumption in data centers has seen a drastic increase in recent years. In data centers, server racks are cooled down in an indirect way by air-conditioning systems installed to cool the entire server room. This air cooling method is inefficient as information technology (IT) equipment is insufficiently cooled down, whereas the room is overcooled. The development of countermeasures for heat generated by IT equipment is one of the urgent tasks to be accomplished. We, therefore, proposed new liquid cooling systems in which IT equipment is cooled down directly and exhaust heat is not radiated into the server room. Three cooling methods have been developed simultaneously. Two of them involve direct cooling; a cooling jacket is directly attached to the heat source (or CPU in this case) and a single-phase heat exchanger or a two-phase heat exchanger is used as the cooling jacket. The other method involves indirect cooling; heat generated by CPU is transported to the outside of the chassis through flat heat pipes and the condensation sections of the heat pipes are cooled down by coolant with liquid manifold. Verification tests have been conducted by using commercial server racks to which these cooling methods are applied while investigating five R&D components that constitute our liquid cooling systems: the single-phase heat exchanger, the two-phase heat exchanger, high performance flat heat pipes, nanofluid technology, and the plug-in connector. As a result, a 44–53% reduction in energy consumption of cooling facilities with the single-phase cooling system and a 42–50% reduction with the flat heat pipe cooling system were realized compared with conventional air cooling system.

Publisher

ASME International

Subject

Fluid Flow and Transfer Processes,General Engineering,Condensed Matter Physics,General Materials Science

Reference28 articles.

1. MIC Research Institute Ltd., 2010, “Survey on Datacenter Electricity Consumption and Green IT FY2010,” in Japanese.

2. The Green Grid, 2009, “Fundamentals of Data Center Power and Cooling Efficiency Zones,” White Paper #21.

3. Airflow Distribution Through Perforated Tiles in Raised-Floor Data Centers;Karki;Build. Environ.

4. Strategies for Effective Use of Exergy-Based Modeling of Data Center Thermal Management Systems;McAllister;Microelectron. J.

5. Measurements and Predictions of the Air Distribution Systems in High Compute Density (Internet) Data Centers;Cho;Energy Build.

Cited by 11 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献