Measurement of the Thermal Performance of a Single-Phase Immersion Cooled Server at Elevated Temperatures for Prolonged Time

Author:

Bansode Pratik V.1,Shah Jimil M.1,Gupta Gautam1,Agonafer Dereje1,Patel Harsh2,Roe David2,Tufty Rick2

Affiliation:

1. University of Texas at Arlington, Arlington, TX

2. LiquidCool Solutions, Rochester, MN

Abstract

Fully immersion of servers in electrically nonconductive (dielectric) fluid has recently become a promising technique for minimizing cooling energy consumption in data centers. The improved thermal properties of these dielectric fluids facilitate considerable savings in both upfront and operating cost over traditional air-cooling. This technology provides an opportunity for accommodating increased power densities. It also minimizes the common operational issues of air cooling technique like overheating and temperature swing in the system, fan failures, dust, air quality, and corrosion. This paper presents various data about the thermal performance of a fully single-phase dielectric fluid immersed server over wide temperature ranges (environment temperatures) from 25°C to 55°C for prolonged periods in an environmental chamber. This work explores the effects of high temperatures on the performance of a server and other components like pump, along with potential issues associated with extreme climatic conditions. The experimental data serves as a means to determine failure criteria for the server and pump by subjecting the system to accelerated thermal aging conditions i.e. around 55°C, consequently simulating the most extreme environmental condition that the server may encounter. Connector seals are inspected for expected degradation upon temperature cycling typically at such extreme conditions. Throttling limit for the server and pump power draw for different temperatures was determined to assess pump performance. Determining the relations between component behavior and operating temperature provides an accurate measure of lifetime of a server. The scope of this paper can be expanded by reviewing the effects of low temperatures on server and component performance. Changes to various performance parameters like power draw of pump and server at the higher and the lower operating temperatures and an understanding of issues like condensation can be used to quantify upper and lower limits for pump and server performance.

Publisher

American Society of Mechanical Engineers

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3