Thermal Performance and Efficiency of a Mineral Oil Immersed Server Over Varied Environmental Operating Conditions

Author:

Eiland Richard1,Edward Fernandes John1,Vallejo Marianna2,Siddarth Ashwin1,Agonafer Dereje3,Mulay Verrendra4

Affiliation:

1. Department of Mechanical and Aerospace Engineering, University of Texas at Arlington, P.O. Box 19023, Arlington, TX 76013 e-mail:

2. CH2M, 2020 SW 4th Avenue, Street 300, Portland, OR 97201 e-mail:

3. Fellow ASME Department of Mechanical and Aerospace Engineering, University of Texas at Arlington, P.O. Box 19023, Arlington, TX 76013 e-mail:

4. Facebook Inc., Menlo Park, CA 425081 e-mail:

Abstract

Complete immersion of servers in dielectric mineral oil has recently become a promising technique for minimizing cooling energy consumption in data centers. However, a lack of sufficient published data and long-term documentation of oil immersion cooling performance make most data center operators hesitant to apply these approaches to their mission critical facilities. In this study, a single server was fully submerged horizontally in mineral oil. Experiments were conducted to observe the effects of varying the volumetric flow rate and oil inlet temperature on thermal performance and power consumption of the server. Specifically, temperature measurements of the central processing units (CPUs), motherboard (MB) components, and bulk fluid were recorded at steady-state conditions. These results provide an initial bounding envelope of environmental conditions suitable for an oil immersion data center. Comparing with results from baseline tests performed with traditional air cooling, the technology shows a 34.4% reduction in the thermal resistance of the system. Overall, the cooling loop was able to achieve partial power usage effectiveness (pPUECooling) values as low as 1.03. This server level study provides a preview of possible facility energy savings by utilizing high temperature, low flow rate oil for cooling. A discussion on additional opportunities for optimization of information technology (IT) hardware and implementation of oil cooling is also included.

Funder

National Science Foundation

Publisher

ASME International

Subject

Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials