Affiliation:
1. Department of Mechanical Engineering, Naval Postgraduate School, Monterey, CA 93943
Abstract
Heat transfer measurements were made during nucleate boiling of R-113 from a bundle of 15 electrically heated, smooth copper tubes arranged in an equilateral triangular pitch. The bundle was designed to simulate a portion of a refrigeration system flooded-tube evaporator. The outside diameter of the tubes was 15.9 mm, and the tube pitch was 19.1 mm. Five of the tubes that were oriented in a vertical array on the centerline of the bundle were each instrumented with six wall thermocouples to obtain an average wall temperature and a resultant average heat transfer coefficient. All tests were performed at atmospheric pressure. The majority of the data were obtained with increasing heat flux to study the onset of nucleate boiling and the influence of surface “history” upon boiling heat transfer. Data taken during increasing heat flux showed that incipient boiling was dependent upon the number of tubes in operation. The operation of lower tubes in the bundle decreased the incipient boiling heat flux and wall superheat of the upper tubes, and generally increased the boiling heat transfer coefficients of the upper tubes at low heat fluxes where natural convection effects are important. The boiling data confirmed that the average heat transfer coefficient for a smooth-tube bundle is larger than obtained for a single tube.
Subject
Mechanical Engineering,Mechanics of Materials,Condensed Matter Physics,General Materials Science
Cited by
23 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献