Affiliation:
1. Rensselaer Polytechnic Institute, Troy, NY
Abstract
The heat transfer performance of two microjet arrays using degassed deionized water was investigated. The in-line jet arrays had a spacing of 250 μm, a standoff of 200 μm, and diameters of 54 and 112 μm. Average heat transfer coefficients were obtained for 150 < Red < 3300 and ranged from 80,000 to 414,000 W/m2-K. A heat flux of 1,110 W/cm2 was attained with 23 °C water and a surface temperature of 50 °C.