Affiliation:
1. CHAM of North America Incorporated, Huntsville, Ala. 35810
2. Electric Power Research Institute, Palo Alto, Calif. 94303
Abstract
This paper presents several applications of the mathematical model described in Part 1 of the paper. Natural and mechanical draft towers of counterflow and crossflow arrangement have been considered. Predicted thermal performances compare well with the available data from operating towers. The distributions of air velocities, pressure, temperature, moisture fraction, and water temperature have been assessed from the considerations of physical plausibility only, since no experimental data are available for comparison. Some sample parametric computations for a mechanical draft crossflow tower are also presented. The parameters studied are: (a) air travel dimension of fill; (b) aspect ratio of fill; (c) fan power; and (d) atmospheric pressure. The results are self-consistent and demonstrate the applicability of the model as an analysis tool.
Subject
Mechanical Engineering,Mechanics of Materials,Condensed Matter Physics,General Materials Science
Cited by
30 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献