Improved Computational Fluid Dynamics Model for Open-Aisle Air-Cooled Data Center Simulations

Author:

Abdelmaksoud Waleed A.1,Dang Thong Q.2,Ezzat Khalifa H.3,Schmidt Roger R.4

Affiliation:

1. Research Assistant e-mail:

2. Professor

3. NYSTAR Distinguished Professor Fellow ASME Department of Mechanical and Aerospace Engineering, Syracuse University, Syracuse, NY 13244

4. IBM Fellow and Chief Engineer Fellow ASME Data Center Energy Efficiency, IBM Corporation, Poughkeepsie, NY 12601

Abstract

There is a need in the IT industry for CFD models that are capable of accurately predicting the thermal distributions in high power density open-aisle air-cooled data centers for use in the design of these facilities with reduced cooling needs. A recent detailed evaluation of a small data center cell equipped with one high power rack using current CFD practice showed that the CFD results were not accurate. The simulation results exhibited pronounced hot/cold spots in the data center while the test data were much more diffused, indicating that the CFD model under-predicted the mixing process between the cold tile flow and the hot rack exhaust flow with the warm room air. In this study, a parametric study was carried out to identify CFD modeling issues that contributed to this error. Through a combined experimental and computational investigation, it was found that the boundary condition imposed at the perforated surfaces (e.g., perforated tiles and rack exhaust door) as fully open surfaces was the main source of error. This method enforces the correct mass flux but the initial jet momentum is under-specified. A momentum source model proposed for these perforated surfaces is found to improve the CFD results significantly. Another CFD modeling refinement shown to improve CFD predictions is the inclusion of some large-scale geometrical features of the perforated surfaces (e.g., lands/gaps) in the CFD model, but this refinement requires the use of grids finer than those typically used in practice.

Publisher

ASME International

Subject

Electrical and Electronic Engineering,Computer Science Applications,Mechanics of Materials,Electronic, Optical and Magnetic Materials

Reference28 articles.

1. Environmental Guidelines for Datacom Equipment;ASHRAE,2008

2. Datacom Equipment Power Trends and Cooling Applications;ASHRAE,2005

3. Liquid Cooling Guidelines for Datacom Equipment Centers;ASHRAE,2006

4. High Density Data Centers: Case Studies and Best Practices;ASHRAE,2008

5. Thermal Profile of a High Density Data Center—Hot Spot Heat Fluxes of 512 Watts/ft2;ASHRAE Trans.,2005