Affiliation:
1. Illinois Institute of Technology, Chicago, Ill. 60616
Abstract
A cross-cooled desiccant dehumidifier prototype was constructed and tested. The cross-cooled dehumidifier prototype was constructed in the form of a cube with a side dimension of 0.6 m. The cooling was achieved by passing air through rectangular channels perpendicular to the process channels which are lined with desiccant sheets consisting of 9 μm Syloid 63™ silica gel held in a Teflon web. The process for the manufacture of the silica gel sheets was developed at the Illinois Institute of Technology. The performance of the dehumidifier prototype was parametrically studied in a test bed that simulates the performance of a cross-cooled desiccant cooling system. The system was tested over a range of operating conditions typically encountered in field installations of such systems. The performance parameters studied are moisture cycled, cooling capacity, and coefficient of performance.
Subject
Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment