Abstract

Abstract A system combining the ventilated concrete floor (VCF) with solar air collector (SAC) in buildings has been applied in the western Sichuan Plateau for nighttime heating. However, the dynamic model coupled with uneven solar radiation of SAC-VCF is absent, thus the thermal behavior of the system is difficult to predict in practice. In this research, a coupled model is built to predict the thermal characteristics of the room with the SAC-VCF system under uneven solar radiation. The calculation model of VCF considers the uneven distribution of solar radiation on the floor surface, established by combining the resistance–capacitance (RC) network model and the number of transfer unit (NTU) model using the discrete method and validated by experimental data. A 3R2C model is utilized to model envelopes, validated by simulation results. The calculation error of surface temperature and room air temperature is within 5%. Then a case study is conducted with the validated model to predict the thermal performance of the SAC-VCF system with even and uneven solar radiation. Results indicate that under uneven solar radiation, the local surface temperature significantly increases to 35.1 °C, 9.1 °C higher than even solar radiation. Meanwhile, under uneven solar radiation, the heat transfer of supply air and surface of VCF is increased by 14% and 6%, respectively. Besides, the room air temperature is almost equal of two cases, while the operative temperature is 0.4 °C lower under uneven solar radiation. The model is beneficial to further study the influencing factors of this system.

Funder

National Natural Science Foundation of China

Publisher

ASME International

Reference46 articles.

1. China Building Energy Consumption Annual Report 2023;China Building Energy Conservation Association and Institute of Urban–Rural Construction and Development, Chongqing University;Constr. Archit.,2024

2. Experimental Investigation on the Heat Transfer Performance of Ventilated Floor With the Influence of Solar Radiation;Luo;Appl. Therm. Eng.,2023

3. Experimental and Simulation Studies on a Single Pass, Double Duct Solar Air Heater;Forson;Energy Convers. Manage.,2003

4. Transient Study (Annual) of the Heat Transfer of a Two-Channel Solar Air Collector;Álvarez;ASME J. Sol. Energy Eng.,2024