Affiliation:
1. Department of Mechanical Engineering, Technische Universiteit Eindhoven, Postbus 513, 5600 MB Eindhoven, The Netherlands
Abstract
When traditional air-to-air cooling is too voluminous, heat exchangers with long thermosyphons offer a good alternative. Experiments with a single thermosyphon with a large length-to-diameter ratio (188) and filled with R-134a are presented and analyzed. Saturation temperatures, filling ratios, and angles of inclination have been varied in wide ranges. A higher sensitivity of evaporation heat transfer coefficients on reduced pressure than in previous work has been found. Measurements revealed the effect of pressure or the saturation temperature on condensation heat transfer. The condensate film Reynolds number that marks a transition from one condensation heat transfer regime to another is found to depend on pressure. This effect was not accounted for by correlations from the literature. New correlations are presented to predict condensation and evaporation heat transfer rates.
Subject
Mechanical Engineering,Mechanics of Materials,Condensed Matter Physics,General Materials Science
Reference23 articles.
1. Investigation of Thermal Performance of an Air-to-Air Thermosyphon Heat Exchanger Using ε-NTU Method;Noie;Appl. Therm. Eng.
2. Waste Heat Recovery Using Heat Pipe Heat Exchanger (HPHE) for Surgery Rooms in Hospitals;Noie-Baghban;Appl. Therm. Eng.
3. Air Heat Exchangers With Long Heat Pipes: Experiments and Predictions;Hagens;Appl. Therm. Eng.
4. A Study of Flow Patterns in a Thermosyphon for Compact Heat Exchanger Applications;Grooten
5. Heat Pipes in Modern Heat Exchangers;Vasiliev;Appl. Therm. Eng.
Cited by
10 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献