An ionic-liquid (IL) is a salt in a liquid state usually with an organic cation and inorganic anion. ILs provide an alternative to the normally toxic working fluids in absorption systems, such as the ammonia/water system. They also eliminate the problems of poor temperature match, crystallization and metal-compatibility problems of the water/LiBr system. In the present study, an IL is explored the working fluid of a miniature absorption refrigeration system so as to utilize waste-heat within the system for low-cost, high-power electronics cooling. To determine performance benchmarks for the refrigerant/IL (e.g. [bmim][PF6]) pairs, system-level simulations have been carried out. An NRTL model was built and used to predict the solubility of the mixture as well as the mixture properties such as enthalpy and entropy. The properties of the refrigerants were determined using REFPROP 6.0. Saturation temperatures at the evaporator and condenser were 25°C and 50°C, respectively. Chip power was fixed at 100 W with the operating temperature set at 85°C. R32 gave the highest operating efficiency with the maximum coefficient of performance (COP) of ca. 0.55 while R134a and R152a showed comparable performance with the maximum COP of ca. 0.4 at the desorber outlet temperature of 80°C. When waste-heat is available for the system operation, R134a and R152a COPs were comparable or better than that of R32.