Research on Autopsy Results of over 10 Year Old Low Pressure Hollow Fiber Membrane from Domestic Water Treatment Plant

Author:

Yoon SukminORCID,Lee Young-JooORCID,Kim Seong-SuORCID,Choi Han-Bong,Park No-SukORCID

Abstract

Objectives : In this study, membrane autopsy was performed for a parallel arrayed low-pressure membrane (microfiltration) filtration process that is actually applied to water treatment, to check out whether there are differences in the degree of membrane fouling due to the uneven flow rate into each module. Also, membrane foulants were evaluated quantitatively.Methods : In this study, autopsy was performed for over 10 year old membranes used for drinking water purification. In this way, the outer casings of membrane modules at different positions were disassembled and visually observed. In addition, In addition, the size of the pores and the porosity were investigated by taking a SEM (Scanning Electron Microscope) photograph for the new and the used membrane module fiber samples in different positions from the header pipe. The used membrane foulants were classified into organic and inorganic matters and quantitatively analyzed.Results and Discussion : As a result of visually observing inside the membrane module that has produced drinking water for over 10 years, the inside of the No. 1 membrane module close to the inlet was contaminated with black foulants. On the other hand, in the case of No. 10 membrane module located farthest from the header pipe inlet, no foulants were observed with the naked eye. Also, it was observed from SEM photograph results that there were large differences in the surfaces among No. 1, 4, 6, 8 and 10 MF module fibers.Conclusion : Even after periodic physical and chemical cleaning, it was concluded that the fouling levels were different each other in the parallel arrayed low-pressure membrane modules. In addition, the pore size distribution and porosities of the membrane modules may vary depending on the position.

Funder

Ministry of Science and ICT

National Research Foundation of Korea

Ministry of Education

Publisher

Korean Society of Environmental Engineering

Subject

General Medicine

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3